All Invertek drives (Except Elevator) are sui with Variable Torque loads and applications.
For Optidrive E2 Variable Torque Mode
– Set P-28 = 25% of P-07
– Set P-29 = 50% of P-09
For Optidrive E3
– Either use the same method as E3
– Or select Fan or Pump Mode in P-13
For Optidrive P2
– Set P4-10 = 50% of P1-09
– Set P4-11 = 25% of P1-07
For Optidrive Eco
– Set P4-01 = 0